N 568/81 KNX Room actuator 24-fold, 24 x AC 230 V, 10 A, multifunctional 5WG1568-1AB81 — Siemens | Futurasmus KNX Group
N 568/81 KNX Room actuator 24-fold, 24 x AC 230 V, 10 A, multifunctional
Manufacturer device name
Description
One relay contact per output as switching element
For controlling drives with AC motor for AC 230 V or DC motor for DC 30 V
For controlling electrothermal/electromotive actuators for AC 230 V
For controlling ventilation motors via up to 3 stages
Rated contact operating voltage: AC 230 V
Rated contact frequency: 50/60 Hz
Rated contact current: 10 A
Rated contact operating voltage: DC 30 V
Screw terminals for connecting stranded wires or single-wire conductors with a conductor cross-section of 0.2 to 5.2 mm²
Direct operation per channel on the device for activating the switching output, moving the solar protection up/down, stop command, slat adjustment, opening/closing the valve, setting the fan speed
Status LEDs on the device for each channel to display the switching status, moving time up/down and upper/lower end position, valve open/closed, fan level
Button on the front of the device for activating/deactivating direct operation and LED for status display
Bus-powered electronics
Housing: plastic, color light grey, N dimension
DIN rail mounting device for mounting on TH35 DIN EN 60715 mounting rail
Protection class: IP 20
Max. width 12 MU
Additional functionalities GAMMA
Selectable operating mode (24 channel switching output/12 solar protection channels AC 230 V/2 solar protection channels DC 30 V/24 channel valve control/6 fan controls)
One switching/status object per output
Adjustable relay operating mode, switch-on/switch-off delay, staircase function, flashing, central function, scene control, logic operations, forced control, operating hours counting
Selectable blind/shutter operating mode
Per channel move commands, stop shading/slat adjustment
Per channel direct movement to a position of the sunblind/blind slats
Per channel central movement, scene control
Differentiation between manual/automatic operation with automatic sunshine function
Adjustable behavior for safety functions
Per fan control adjustable 3 fan stages, fan operating mode, switch-off delay, start behavior, forced control, automatic function, control value monitoring
Per valve control selectable 2-/3-point valve
Per valve control, adjustable heating/cooling operating mode, direction of valve control, control via two-point-/continuous control, control value monitoring