KNXDALI Gateway Twin N 14132 5WG1141-1AB32 — Siemens | Futurasmus KNX Group
KNXDALI Gateway Twin N 14132
Manufacturer device name
Description
DALI Multi-Master Controller with DALI-2 certification acc. to IEC 62386-101 -103 and two DALI outputs that communicate with up to 128 DALI ECG Ed.1 and DALI-2 and 16 DALI-2 presence and 16 brightness sensors
For communication via KNX with electronic ballasts (ECG) with a DALI interface
Support of ECG type 0, 1, 2, 3, 4, 5, 6, 7, and 8 acc. to IEC 62386 edition 1 and edition 2 (DALI-2)
Supports presence (part 303) and brightness (part 304) DALI-2 sensors
Support of DALI DT8 ECG for color temperature Tc Tunable White and color control RGB, RGB(W)
IP-interface and Ethernet connection via RJ45 port
KNX Data Secure ready
Integrated power supply with input voltage AC 220-240 V, 50-60 Hz or DC 220-240 V for powering the gateway electronics and DALI output
Maximum DALI output voltage of 19 V, short circuit resistant
Incorrect voltage detection during commissioning if incorrect power line is connected to a DALI output
Configurable 7 segment display for displaying operation mode and error messages
Pushbutton for switching between bus and direct operating mode
LED indicate status of direct operation, IP connection and error for each DALI output
One pair of pushbuttons for switching On/Off and dimming of all connected DALI ECG
Configurable assignment of max. 128 DALI ECG to 128 intelligent channels with automatic group creation
Each intelligent channel is independently controlled (switching, dimming, set dimming value, color and color temperature), offering 2 logic functions, multiple overrides, night mode, feedback for channel status and lamp failure
Control of all connected luminaries together in broadcast mode
Status signal and display of lamp and ECG failure per group and per DALI device
Object to monitor device function
Works function for switching and dimming
One or two level timer
Counter for switching cycles and operation hours including threshold monitoring
Energy saving function with 32 stand-by-area analysis for activation of switch actuators
Scene control for up to 32 DALI scenes
16 integrated independent 2-level-controllers for brightness control and 16 independent constant light level controllers for 1 main luminaries group and up to 4 additional luminaries groups
16 integrated calculators for brightness (internal and external) values
Assignment of DALI ECG to channels/groups and with test options of channels/groups and scenes via DCA in ETS during commissioning of gateway
Assignment of DALI sensors and test option of sensors via DCA in ETS
Integrated bus coupling unit
bus connection via bus terminal
Maintenance-free push-in terminals for connection and through-wiring of untreated single-core, stranded or multi-core conductors, 0.5 ... 2.5 mm²
Mounting on DIN rail EN 60715-TH35-7.5
Additional functionalities GAMMA
Configurable assignment of max. 64 DALI ECG per DALI line to 64 intelligent channels with automatic group creation
Each channel is independently controlled (switching, dimming, set dimming value, color and color temperature), offering 2 logic functions, multiple overrides, night mode, feedback for channel status and lamp failure
Support of DALI DT8 ECG for color temperature Tc Tunable White and color control RGB, RGB(W)
Supports presence (part 303) and brightness (part 304) DALI sensors