MANUFACTURER DEVICE NAME
EMU superior KNX DIN RAIL electricity meter, for current transformers, KNX standard and KNX quick
Producto descatalogado — Este producto está descatalogado por el fabricante; puede no estar disponible o solo bajo pedido.
FUTURASMUS DEVICE NAME: KNX energy counter, active / reactive, bidirectional / cos phi, EZ-EMU-WSUP-D-REG-FW, con toroidal connection, for three-phase current, 4 tariffs, DIN rail, serie EMU superior, Ref. 87774
INFORMACIÓN DEL FABRICANTE
| Brand | : Lingg&Janke |
| Reference | : 87774 |
| Family | : smart-metering |
| Color | : |
| Warranty | : 2 years |
| Return allowed | : No |
MORE MANUFACTURER INFORMATION
| Series | : EMU superior |
| Price group | : 4 |
| EAN code | : 4260049682636 |
| NC/TARIC code | : 90283019 |
| Country of origin | : DE |
| Net weight | : 34 g |
| Gross weight | : 34 g |
| Length | : 9.5 cm |
| Width | : 9.5 cm |
| Height | : 7.8 cm |
SPECIFICATIONS
- INTERFACE
- KNX
- MOUNTING
- DIN rail
- COUNTER
- Energy
- NR. OF PHASES
- Three-phase
- TARIFF
- 4 tariffs
- MEASUREMENT TYPE
- ActiveCos phiReactivebidirectional
- 230V CONNECTION
- Toroidal connection
DESCRIPCIÓN
EMU superior KNX DIN RAIL electricity meter, for current transformers, KNX standard and KNX quick
- - bidirectional 3 phase electricity meter
- - active and reactive energy, active and reactive power, voltage, current, power factor, 4 tariffs
- - current transformer ratio selectable for 1A (max. 4000/1) and 5A (max. 20000/5)
- - 4 additional switching outputs
- - with integrated KNX bus coupling unit, KNX quick included
- - full FacilityWeb functionality
- - price including calibration fee
- - programmable via ETS with coding switches set to 0
- - ETS application: EZD_FW_en_de_22.knxprod, type 9a
Envíanos tu consulta sobre este producto
Inicia sesión para enviar una consulta.
Inicia sesión para enviar una valoración.
VALORACIONES
Cargando valoraciones…
Frequently asked questions about this product
1What toroidal transformers can be used with EMU meters?
- Toroidal transformers can be used within the following ranges: - 5 / 5A to 20000 / 5A - 1 / 1A up to 4000 / 1A Example 1. A 125KW installation would be around 190A, so transformers with a 250 / 5A ratio (recommended) or 250 / 1A could be used
Can't find your question?